Share this post
Key takeaways from this article:
You have the customer's meter load profile. Perhaps a PV generation profile as well, sometimes the grid feed-in. What you don't have is the actual consumption.
That sounds like a detail. It is the basis of your design.
Grid consumption is a result, not a cause. It shows what is left after self-consumption. But the storage system does not work on the remainder. It works on consumption.
What you actually have on the table in a project
In practice, the data situation in C&I projects usually looks like this:
- A grid consumption profile in 15-minute resolution, usually covering twelve months
- Sometimes a PV generation profile from the inverter or monitoring
- Sometimes a grid feed-in profile from the Direktvermarktung (selling generated power via a direct marketer under the German EEG) or EEG settlement
- Almost never a consumption load profile
Where an existing system is running, consumption is systematically missing. Exactly where the storage system is most relevant.
Why the difference shifts the sizing
If you calculate on grid consumption, you do not see the load level covered by PV. Everything the system already absorbs is invisible in your data.
Three effects follow from this, and all three point in the same direction:
The self-consumption potential is underestimated. The storage system is meant to shift PV surplus into hours of high consumption. How much arrives there depends on consumption, not on residual grid consumption.
The load peaks are misplaced. Grid consumption peaks occur where load is high and PV is low. Consumption peaks occur elsewhere. For the design of the storage power, that is a difference of several hundred kilowatts.
The expansion cannot be calculated. Once additional PV, charging infrastructure or a heat pump is added, the residual profile changes completely. Without consumption, you cannot calculate this case properly, because you lack the starting point.
The result is rarely a gross error. It is a quiet shift that goes unnoticed in the quote but not in operation.
The usual workarounds and where they break
Estimating. Consumption equals grid consumption plus a roughly assumed self-consumption. It works as long as nobody checks the calculation.
Standard load profiles. A standard load profile represents an industry average, not a site. For peak shaving that is useless, because the deviation from the average is exactly what creates the peak.
Artificial PV profiles. A synthetic generation profile is scaled until the balance roughly fits. That produces a number, but no traceability. If the customer asks where the consumption comes from, there is no answer other than the assumption.
For sales, that is the real damage. Not the deviation, but the missing justification.
Reconstruction using the energy balance
The clean approach uses the values that are actually documented. Settlement data is exact, even if the profiles are not.
The principle: real energy volumes are set as target values, and the profiles are fitted to them automatically.
The annual energy fed into the grid is shown in the Direktvermarktung settlement. Grid consumption is shown on the electricity bill. Neither is an assumption, both are billed values. From the balance of grid consumption, generation and grid feed-in, you get consumption at 15-minute resolution, consistent with all known energy volumes.
No manual adjustment, no tweaking of curves, no scaled stand-in profiles.
The decisive point is verifiability. Every variable in the model can be checked against a document that the customer owns.
What you can read from the load profile afterwards
Once consumption is in place, data preparation becomes a site assessment. Straight from a CSV, without preparatory work:
- Load peak. The value your demand charge depends on.
- Base load. How much load is present all year round, regardless of production and season.
- Utilisation hours. Tells you whether the use case is driven by power or by energy. And whether the 2.500-Stunden-Regelung (German rule for reduced grid fees at 2,500 or more annual usage hours) under Section 19 StromNEV is even within reach. If not, you can skip the check.
- Atypical usage potential. The HLZF (high-load time windows set by the German grid operator) of the relevant grid operator can be checked directly against the load profile.
- PV coverage potential. How much of the consumption the generation realistically covers, time-resolved rather than as an annual total.
These key figures decide which use cases you pursue at all. But they are only useful if they are based on consumption and not on residual grid consumption.
And then the calculation begins
On this basis, you can compare the strategies directly against each other instead of guessing at them one after another:
- Self-consumption optimisation
- Peak shaving
- Both combined
Only this comparison shows where the storage size really ends up. It regularly differs from the rule of thumb, and it differs from the calculation based on grid consumption.
What this means for your process
The order is not negotiable. Calibrate the starting point first, then optimise. Every variant calculation inherits the quality of its starting point.
If you estimate consumption, you optimise precisely on an inaccurate model. The result looks robust. It isn't.
In the webinar: the complete process at a real site
{{cta}}
Do you want to see your own site? 30-minute introductory call, free of charge and without obligation.
We use AI to support research, structuring and language editing. minimum.energy is responsible for the technical content, classification and approval. Figures, claims and project-specific statements are checked before publication.
Commercial and industrial (C&I): retrofitting BESS, Multi-Use scenarios
Industrial site in NRW with 9.3 GWh consumption and existing PV: three storage system scenarios across two grid fees regimes. The smaller storage system with a dynamic tariff beats 5 MWh Multi-Use.
323k
1.1 yrs
2.86M
-23%
Webinar recording
Felix and Leon show in the software how actual consumption is reconstructed from grid consumption, generation and grid feed-in. Then the calculations run directly on that basis: load profile analysis, atypical usage check and the comparison of self-consumption optimisation, peak shaving and combined operation. 45 minutes, straight from the software, without endless slides.





