Design meets reality. A storage system project put to the practical test.

Designed for cost reductions of up to 66%, 63% achieved in live operation. Six months of operating data show how much of the design carries through and where the gap comes from.
iPhone mockup
Dashboard mockupDashboard mockup

93% of the possible saving. The rest has causes.

Whether a storage system delivers what the business case promises only becomes clear in operation. Comparing forecast and measurement is not enough, because consumption, generation and prices rarely turn out as assumed. In Hebertsfelden, we therefore applied a second benchmark: the optimum under the conditions that actually occurred. A farm with 99.62 kWp of PV, a 225 kWh storage system and a 32 kW target peak. 1PUNKT5 designed and built it, be.storaged controls it with okean, and minimum energy ran the calculations before and after, using the same model.

Three findings from the case study:

  • The design is confirmed in live operation. The design target was a cost reduction of up to 66% compared with grid consumption alone. Under the actual conditions in 2026, up to 68% would have been possible. 63% was achieved.
  • The gap has known causes. Three times the battery did not follow the control system's command. In April it was unreachable 30% of the time. Twice, PV curtailment hit a nearly empty storage system. The rest is the price of forecasting.
  • In everyday use, the storage system delivers. In 99.75% of quarter-hours, grid consumption was at or below the target peak of 32 kW. On average, charging took place at €44 per MWh and discharging at €147 per MWh.

You also get the methodology so you can reproduce the calculations, and five points we are taking into the design for 2027. We will discuss the results on 22 October in the webinar with 1PUNKT5 and be.storaged.

Download the white paper for free

Commercial and industrial (C&I): retrofitting BESS, Multi-Use scenarios

Industrial site in NRW with 9.3 GWh consumption and existing PV: three storage system scenarios across two grid fees regimes. The smaller storage system with a dynamic tariff beats 5 MWh Multi-Use.

323k

Initial investment

1.1 yrs

Payback period

2.86M

Electricity costs year 1

-23%

Electricity costs year 1
View Use Case →

AgNes capacity charge: what happens to the peak shaving calculation from 2029

Same site, same storage system, new grid fee system: the value contribution from peak shaving falls from €19,602/a to minus €4,258/a. The return falls from 11.8 to around 7 per cent.

11,8%

Return until 2028

7,3%

Return from 2029

-100%

Additional costs p.a. from AgNes

43.5k

Additional costs p.a. from AgNes
View Use Case →

Payback period for photovoltaics and battery storage for an industrial business

An industrial business wants to invest comprehensively in PV, storage and charging infrastructure for the first time. This is how the ROI is calculated.

28,9%

Return

3.5 yrs

Payback period

294.2k

Savings over 20 yrs

951.1k

Savings over 20 yrs
View Use Case →