Commissioning & parameterisation

After the simulation comes the critical step into practice: translating the model into real control parameters. The aim is to carry the peak reduction and SoC strategy calculated in advance reliably into operation.

Step 1: Function test & comparison

Before control operation starts, the system is verified with historical load profile data. The simulated peaks are compared with the actual values from the metering points. If the timing and magnitude of the expected peaks match, the control concept is approved.

Step 2: Parameterisation

The most important starting parameters are taken from the simulation, but they must be adapted to the real behaviour of the consumers:

  • Setpoint power: maximum target power at the grid connection point (e.g. 1,200 kW).

  • Droop curve: ratio between the deviation from the setpoint and the discharge power of the storage system.

  • SoC reserve: minimum state of charge that is guaranteed to be available even during HLZF (high-load time windows set by the German grid operator).

  • Rebound limit: limit on the recharging power after a peak to prevent new peaks.

Step 3: Trial operation

In the first month of operation, the control is monitored closely. Deviations between target and actual peaks are analysed and parameters are readjusted (fine-tuning). Documenting this test phase matters if the operation falls under an individual grid fee agreement (§ 19 StromNEV), as it serves as evidence of stable and cost-reflective grid usage.

Practical tip: A simple “plan vs. actual” visualisation (peak reduction, SoC curve, rebound events) helps you monitor the control status transparently and spot errors in the EMS early.

Operating strategies & optimisation

After commissioning, the right control strategy determines how stable and economical peak shaving is. Three basic principles have become established:

1. SoC management (state of charge)

The state of charge of the storage system is the decisive factor for reliability.

  • Reserve planning: A defined minimum SoC (e.g. 30%) ensures that enough energy is available during HLZF hours or for unexpected peaks.

  • Pre-charge: Before expected peak times, the storage system is deliberately charged, even if the electricity price is higher. Avoiding the peak saves more than the more expensive energy costs.

  • SoC window: The typical usable range is 20 to 90%. Below 20%, power output tends to drop, and above 90%, charging efficiency falls.

2. Rebound avoidance

After a peak event, the storage system must not recharge fully straight away, otherwise a second peak occurs.

  • Solution: time-shifted or PV-led recharging.

  • Control parameters: maximum recharging power (e.g. 50% of rated power) and lockout periods (e.g. 30 min after discharge).

  • With HLZF tariffs: rebound lockout until the end of the time window.

3. Cycle and efficiency optimisation

Every unnecessary discharge costs cycle life and efficiency.

  • Droop control: linear power output depending on the deviation from the setpoint. This protects the battery and reduces switching operations.

  • Prioritisation in Multi-Use: 1) grid protection, 2) peak shaving, 3) self-consumption, 4) arbitrage.

  • Forecast-based optimisation: Integrating weather and production data enables predictive SoC planning and reduces redundant cycles.

Example: A metalworking plant with an HLZF from 17:00 to 19:00 uses the EMS to bring the storage system to 90% SoC from 16:00 and to recharge only after 19:00. Peak reduced, rebound avoided.

Monitoring & KPIs

A working peak shaving system is not a “fire-and-forget” project. Only if you measure and evaluate continuously can you spot deviations early.

Primary performance indicators (monthly/annual)

  • Avoided load peak [kW]: difference between measured and simulated peak.

  • Savings [€]: demand charge × avoided kW.

  • HLZF hit rate [%]: share of hours in which the reserve was sufficient.

  • SoC utilisation [%]: ratio of used to available capacity.

  • Cost per cycle [€/cycle]: operating costs per charge/discharge.

Secondary indicators

  • Temperature, efficiency, cell voltage, communication errors.

  • Meter deviations between the EMS and the grid operator (calibration is important).

Visualisation & reporting

Dashboards should show peak reduction, SoC and rebound events in real time. Traffic light logic makes sense, for example:

  • Green: Target values stable.

  • Yellow: Deviation >10%.

  • Red: Peak above target value or SoC reserve undercut.

Practical tip: Monthly reporting to the energy manager plus annual documentation for the § 19 evidence.

Maintenance & operational reliability

Technical stability determines the ROI. The battery, measurement systems and communication must run reliably at all times.

Battery & power electronics

  • Maintenance cycles: visual inspection, cell voltage balancing, temperature check.

  • Firmware updates: install regularly (observe manufacturer approval).

  • Performance test: controlled discharge once a year to verify capacity.

Communication & data security

  • Continuous monitoring of connections (EMS ↔ BMS ↔ SCADA).

  • Alarm if data points fail or signals are delayed.

  • Backup strategy: daily export of load and control data.

Fallback & emergency operation

  • Defined limits: in case of a communication error → peak limit = conservative setpoint.

  • Production stays protected. The storage system switches to standby instead of reacting in an uncontrolled way.

  • For atypische Netznutzung (atypical grid usage under § 19(2) StromNEV, reduced grid fees for shifting load out of HLZF): secure the log files as evidence for 3 years.

Note: For special fees (§ 19 StromNEV), grid operators often require evidence of “regular, steady operation”.

Continuous improvement & recalibration

After a few months, it becomes clear how realistic the original simulation was. The key to lasting success is ongoing adjustment.

Data comparison

  • Comparison: planned vs. actual savings and peak level.

  • Analysis of deviations (public holidays, shift changes, new consumers).

  • Adjust setpoints and SoC reserves accordingly.

Recalibration

  • Annual recalculation of the optimal storage power if production patterns or tariffs change.

  • Integrate new flexible assets (e.g. charging infrastructure) into the EMS to enable combined control.

  • Automated re-tuning via machine learning modules: the EMS learns at which times peaks are most likely.

Process as a PDCA cycle (Plan, Do, Check, Adjust)

  1. Plan: simulation & control strategy.

  2. Do: implementation in operation.

  3. Check: monitoring & KPI analysis.

  4. Adjust: readjust the parameterisation.

Result: stable operation, constant ROI and documented efficiency gains, which matter for compliance and energy audits (ISO 50001).

{{cta}}

Practical example: peak shaving at a mid-sized company

A metalworking company in Baden-Württemberg operates several presses and compressor systems with a total connected load of around 2 MW.

Annual electricity consumption is 11 GWh, so the company meets the requirements of the 2.500-Stunden-Regelung (German rule for reduced grid fees at 2,500 or more annual usage hours) under § 19 StromNEV. The problem: short but high load peaks at the shift changes at 6:00 and 14:00. These quarter-hours previously determined the monthly demand charge and led to unnecessarily high grid fees.

Starting point

  • Maximum 15-minute power: 1,820 kW

  • Annual consumption: 11,000,000 kWh

  • Utilisation hours: 11,000,000 kWh / 1,820 kW ≈ 6,040 h

  • Demand charge: 160 €/kW·a → annual demand charges ≈ €291,000

  • Tariff logic: monthly maximum, 15-min measurement interval, no HLZF

Implementation

After a load profile analysis and simulation with minimum.energy, a battery system with 600 kW power and 500 kWh usable capacity was selected.

  • Control strategy: setpoint 1,200 kW, linear droop curve from 1,200 to 1,800 kW

  • SoC reserve: 25% (HLZF safety)

  • Rebound limit: max. 300 kW recharging power, lockout time 30 min

The system was integrated via the existing EMS (Modbus communication). The control cycle is 1 s, and the data is archived in the SCADA.

Results after 12 months

  • Actual peak: 1,240 kW

  • Reduction: 580 kW → savings ≈ €93,000/a

  • Cycles: avg. 0.7 cycles/day → 250 cycles/year

  • Round-trip efficiency: 89%

  • HLZF hit rate: 100% (SoC never below 25%)

  • Payback period: < 6 years (incl. support under § 19 StromNEV)

Lessons Learned

  • The biggest cost drivers were short, reproducible peaks, not background noise.

  • A conservative SoC buffer (25%) proved more economical than maximum energy utilisation.

  • The automated reporting from minimum.energy served as evidence of cost-reflective grid usage for the grid operator.

  • By integrating further consumers (charging infrastructure, refrigeration system), a second optimisation stage is planned.

Our tip:

With minimum.energy you can test the entire control operation virtually in advance. The platform simulates real load profiles, tariff logic and HLZF hours to the second, including SoC reserves, rebound behaviour and communication delays. This way, before commissioning you can see how the system reacts to peaks, where readjustment is needed and which parameterisation delivers the most stable results in continuous operation.

Test the entire control operation virtually in advance with minimum.energy

We use AI to support research, structuring and language editing. minimum.energy is responsible for the technical content, classification and approval. Figures, claims and project-specific statements are checked before publication.

Ready for quotes that actually hold up?

Bring an example project. In 30 minutes, we will show you how minimum energy transforms your pre-sales process.

Sign up once and stay informed

Email distribution list

Sign up once and stay informed

On this list, we keep you up to date on upcoming webinars, trade fair appearances, new blog posts and glossary entries, as well as our brand-new monthly newsletter covering all product news.
No items found.