Many companies invest a lot of time and money in battery storage or load management without first understanding their grid operator's measurement and billing logic in detail.
The result: simulations and plans built on wrong assumptions, and business cases that do not hold up in operation. The key to reliable peak shaving is a clean data basis and clear analysis.
Understanding measurement & billing
15-min measurement interval
In the C&I sector, load at the grid connection point is almost always measured in a 15-minute grid. What matters is not the short spike lasting seconds, but the highest 15-min average in the billing period.
Example: A site draws 2,000 kW for 3 minutes, then drops back to 1,000 kW. Over the 15-min average, 1,200 kW is what counts, not the 2,000 kW.
Monthly vs. annual maximum
- Monthly maximum: Each month is billed separately. Every monthly peak creates its own demand charge.
- Annual maximum: A single 15-min peak determines the price for the entire year.
Consequence: With an annual maximum, it is often worth protecting against even rare outliers. With a monthly maximum, you need continuous strategies.
HLZF & atypische Netznutzung
- HLZF: In these hours the grid is under particular strain. Load reduction works twice here: a lower peak plus a bonus on grid fees.
- Atypische Netznutzung: Special rules for companies that systematically shift their loads away from grid peaks.
If you ignore HLZF and atypische Netznutzung, you give away considerable savings.
Typical misinterpretations that cost money
- Every spike is a peak: Wrong. What matters is the 15-min average.
- PV automatically covers all peaks: Wrong. Many peaks occur in the morning or evening hours, when PV output is low.
- One trial month is enough: Wrong. With an annual maximum, even a single December peak can decide the annual billing.
- Optimising average load instead of maximum quarter-hourly demand: Wrong. The highest demand is billed, not the average.
{{cta}}
Data basis & analysis
To plan peak shaving reliably, you need a solid data basis. Two elements are decisive: the load profile and the tariff logic.
Load profile data as the foundation
The foundation is the so-called load profile, i.e. the record of energy consumption in a quarter-hourly grid. For a serious analysis, you should have at least twelve months of complete data, ideally several years. Only then can you spot seasonal effects such as summer loads from cooling or extra shifts in winter.
The data must be available in 15-minute intervals (96 or 97 values per day). Quality matters: gaps, duplicate values or incorrect time zones can distort the picture and must be cleaned up before the analysis. It is also essential that the values are measured at the grid connection point, because only there does the demand count for the grid operator. Measurements on sub-meters or partial systems are not relevant for billing.
Tariff logic & seasonality
The second building block is the tariff structure, i.e. the rules by which the grid operator bills. This includes the demand charge (e.g. in €/kW·a or €/kW·month) and the billing mode: monthly or annual maximum. You also need to take into account HLZF, rules on atypische Netznutzung and any special blocking periods.
Besides the demand charge, the energy charge also plays a role, especially if it varies by time of day or season. In many sectors you can spot patterns here: higher peaks in summer because of air conditioning, in the pre-Christmas period because of extra shifts, or in the food industry because of seasonal production peaks.
Why the two belong together
Only the combination of load profile data and tariff logic shows which peaks are actually relevant and expensive. Without this comparison, there is a risk that storage systems or load management systems work against the "wrong" peaks, with high costs but little effect on the bill.
Our tip:
With minimum.energy, you can merge load profiles and tariff logic automatically. The software identifies recurring and tariff-critical peaks, simulates their effect on the bill and shows which storage capacity you really need. That turns measurement data into a clear business case.
We use AI to support research, structuring and language editing. minimum.energy is responsible for the technical content, classification and approval. Figures, claims and project-specific statements are checked before publication.
Sector coupling with BESS for commercial sites: heat pump, battery and thermal storage as one system
Sector coupling with BESS for commercial sites: how a heat pump, BESS and thermal storage as an integrated system save 78% of gas consumption, and how atypische Netznutzung raises the return to 18.5% without additional investment.
18,5%
5.2 yrs
751.2k
-15%
Ready for quotes that actually hold up?
Bring an example project. In 30 minutes, we will show you how minimum energy transforms your pre-sales process.